GRP sectional water tanks are assembled on site from hot-pressed glass-reinforced polyester panels measuring 1 × 1 m. They cover capacities from 1 to over 500 m³ at heights of 1.0 to 5.0 m, with a design life of over 25 years. Al-Asas Al-Thameen handles design, supply, installation, testing and commissioning in Libya, Jordan and Algeria.
Why a GRP Sectional Tank Instead of Steel or Concrete?
- Fits through any door. Panels ship flat — a 100 m³ tank takes up a small fraction of the volume of a welded steel tank, and can be brought onto a roof or into a basement that no pre-built tank could reach.
- Bolted by hand, no welding. Panels are bolted together on site — no crane and no welder needed.
- No rust, no painting. No cathodic protection, and no internal lining that peels off after a few years.
- Thermally insulating. A GRP shell keeps water cooler than steel or concrete through the Libyan summer.
- Expandable and relocatable. Panels can be added to increase capacity, or the tank can be dismantled and rebuilt at another site.
- All wetted parts are suitable for drinking water — GRP panels, SS 316 stays and bolts, and non-toxic PVC foam sealant.
Read the details and animated diagrams in our guide: Benefits of GRP water tanks, from the University of Benghazi project.
Applications
- Drinking-water storage for buildings, communities and municipalities
- Break tanks and roof tanks for booster systems
- Fire-fighting water reserve
- Feed and product tanks for desalination and reverse osmosis plants
- Water storage for irrigation and agriculture
- Process water in food, pharmaceutical and industrial plants
Materials of Construction
| Component | Material | Specification |
|---|---|---|
| Wall, base and roof panels | Hot-pressed GRP | 1000 × 1000 mm module — thickness graded by hydrostatic pressure |
| Panel sealant | Closed-cell PVC foam | 75 × 3 mm and 150 × 3 mm — non-toxic |
| Bolts, nuts and washers | Stainless steel 316 | M10 / M12 — plastic-capped on the wetted side |
| Internal stays | Stainless steel 316 | 12 mm diameter — 1.0 to 5.0 m with SS 316 brackets |
| External reinforcement | Hot-dip galvanized steel or SS 316 | Flat bar 40×3 and 80×3 mm — corner angle 75×75 mm |
| Roof supports | Pultruded FRP | 50 × 50 mm — 1.0 to 4.0 m |
| Nozzles and flanges | Cast polyester | Inlet · outlet · drain · overflow — all standard sizes |
| Ladders | Internal FRP · external galvanized | 1.0 to 4.0 m in 0.5 m steps |
Capacity Table (m³)
Total nominal volume = length × width × height. Allow about 5% freeboard to arrive at the actual working volume. Any size is possible in one-meter increments — the table shows the most common sizes.
| Footprint L × W (m) |
H=1m | H=1.5m | H=2m | H=2.5m | H=3m | H=3.5m | H=4m |
|---|---|---|---|---|---|---|---|
| 2 × 1 | 2.0 | 3.0 | 4.0 | 5.0 | 6.0 | 7.0 | 8.0 |
| 2 × 2 | 4.0 | 6.0 | 8.0 | 10.0 | 12.0 | 14.0 | 16.0 |
| 3 × 2 | 6.0 | 9.0 | 12.0 | 15.0 | 18.0 | 21.0 | 24.0 |
| 3 × 3 | 9.0 | 13.5 | 18.0 | 22.5 | 27.0 | 31.5 | 36.0 |
| 4 × 3 | 12.0 | 18.0 | 24.0 | 30.0 | 36.0 | 42.0 | 48.0 |
| 4 × 4 | 16.0 | 24.0 | 32.0 | 40.0 | 48.0 | 56.0 | 64.0 |
| 5 × 4 | 20.0 | 30.0 | 40.0 | 50.0 | 60.0 | 70.0 | 80.0 |
| 6 × 4 | 24.0 | 36.0 | 48.0 | 60.0 | 72.0 | 84.0 | 96.0 |
| 6 × 5 | 30.0 | 45.0 | 60.0 | 75.0 | 90.0 | 105.0 | 120.0 |
| 8 × 4 | 32.0 | 48.0 | 64.0 | 80.0 | 96.0 | 112.0 | 128.0 |
| 8 × 5 | 40.0 | 60.0 | 80.0 | 100.0 | 120.0 | 140.0 | 160.0 |
| 10 × 5 | 50.0 | 75.0 | 100.0 | 125.0 | 150.0 | 175.0 | 200.0 |
Heights of 4.5 and 5.0 m are available; they require additional external reinforcement and a heavier base, and are quoted per project.
Available Accessories
| Accessory | Material | Size / Range |
|---|---|---|
| Internal ladder | FRP / GRP | 1.0 – 4.0 m in 0.5 m steps |
| External ladder | Galvanized steel | With safety cage on request |
| Water level indicator | Aluminum / PC / stainless steel | 1.5 – 4.0 m — external float with direct reading |
| Air vent | PVC | DN50 / DN100 — with insect-proof mesh cap |
| Manhole and cover | GRP | 600 × 600 mm — lockable with raised rim |
| Roof supports | Pultruded FRP | 1.0 – 4.0 m — for wide spans |
Foundation & Installation Requirements
Concrete Foundation
- Continuous reinforced-concrete plinths or a steel frame beneath every panel joint line, i.e. every one meter.
- Top-surface levelness within 2 mm per meter and 6 mm over any 6 meters — measured both across and diagonally.
- The structural adequacy of the foundation and its design loads are the client’s responsibility.
- Foundation drawings for the selected size are issued with the purchase order.
Clearances
- Leave at least 600 mm on all sides around the tank and 600 mm above it, measured from the external dimensions.
- This space must remain clear after installation for inspection and maintenance.
- If the tank roof is 2.5 m or more above finished floor level, allow space for a ladder tower.
Certifications & Standards
Panels are manufactured to Al-Asas Al-Thameen’s specification at approved factories and comply with the standards and approvals below. Certificates are issued in the name of the producing factory — valid original copies are included in every project file.
| Standard | Details |
|---|---|
| BS 6920-1:2014 Suitability for contact with drinking water |
The British Standard for the suitability of materials in contact with drinking water. Panels are tested and passed for: odor and taste, appearance, growth of aquatic microorganisms, extraction of substances, and extraction of metals. |
| WRAS Approved Material UK Water Regulations Approval Scheme |
GRP water tank panels approved under the UK Water Regulations Approval Scheme for materials in contact with drinking water, with a current approval. |
| TSE K 304 Turkish Standards Institution |
Certificate of conformity for standard water tanks intended for drinking water and general use. |
| ISO 9001:2015 Quality management system |
The producing factory holds a quality management system certification for the production and sale of standard metal and composite water tanks. |
Warranty & Scope of Supply
Warranty: 12 months from delivery against manufacturing defects, provided the tank is installed on a foundation built to the issued drawings and operated within the stated design conditions.
Full scope of service: sizing · foundation drawings · supply · installation · hydrostatic load testing · disinfection · commissioning.
Frequently Asked Questions
Is a GRP tank suitable for drinking water?
Yes. All wetted parts are suitable for drinking water: GRP panels, SS 316 bolts plastic-capped on the inside, and non-toxic PVC foam sealant. The panels also hold the British BS 6920 and WRAS approvals for suitability in contact with drinking water.
How long does installation take?
It depends on capacity and how ready the foundation is. Small and medium tanks are installed within a few days once the foundation is complete. The foundation itself — the client’s responsibility — is usually the critical path in the schedule.
Can the tank capacity be increased later?
Yes, and this is one of the main advantages of the sectional system. Panels can be added to enlarge the tank, provided the foundation was designed or extended to carry the new capacity. The tank can also be fully dismantled and rebuilt at another site.
How does it compare with a welded steel tank?
A steel tank needs a crane and an access opening large enough for the whole tank, plus painting, rust protection and periodic lining maintenance. A GRP sectional tank arrives flat, is bolted together by hand, doesn’t rust or need painting, and insulates thermally — a real advantage in the Libyan summer.
Do you provide concrete foundation drawings?
Yes. The foundation drawing for the selected size is issued with the purchase order, and includes plinth locations and design loads.
Request a Quote for a GRP Tank
Tell us the capacity you need, the space available and the intended use — and we’ll recommend the right size, with the foundation drawing and full technical datasheet.
Technical reference: datasheet ALS-DS-GRP-01 — Al-Asas Al-Thameen for Water Treatment (ALS), Libya · Jordan · Algeria.
Drinking Water & Investment PlantsIndustrial & Factory WaterAgriculture, Irrigation & Poultry FarmsHotels, Facilities & Homes
All ProductsALS 720 AntiscalantALS 710 AntiscalantALS 750 AntiscalantALS 2000S Silica InhibitorALS 780 Membrane CleanerCL 700 Sodium HypochloriteHCL 300 Hydrochloric Acid
Phone: 00218 91 844 4575
WhatsApp: 00218 93 077 8375
Email: info@als-water.com
Branches: Misrata · Tripoli · Amman · Ouargla
Working Hours: 9 AM – 5 PM (Closed Fridays)
Follow us on Facebook